Charge Air System, Checking For Leaks
Charge Air System, Checking for Leaks
Special tools, testers and auxiliary items required
• Testing Unit for Turbo Charger (V.A.G 1687)
• Adapter (V.A.G 1687/5)
- Remove the noise insulation.
- Remove the frame for the noise insulation.
- Release the securing clip - A - and disconnect the hose - B - from the charge air pipe.
- Mount the (V.A.G 1687/5) onto the charge air pipe - A - and turn it approx. 90° - B -.
Prepare the (V.A.G 1687) as follows:
- Remove the pressure regulator valve - 2 - and close valves - 3 and 4 -.
• In order to be able to turn pressure regulator valve - 2 -, rotary knob must be pulled upward.
- Connect the (V.A.G 1687) as illustrated.
- Connect the pressurized air hose - 1 - (pressurized air supply) to the (V.A.G 1687).
• If water is located in viewing glass, drain it via water drain plug - 6 -.
- Open the valve - 3 -.
- Set the pressure to 0.5 bar using the pressure regulator valve - 2 -.
Pressure must not exceed 0.5 bar! A pressure set too high may damage the engine.
- Open the valve - 4 - and wait until the test circuit is filled. Adjust the pressure to 0.5 bar if necessary.
- Inspect the charge air system for poorly sealed areas by listening, feeling, using commercially available leak detection spray or by using the ultrasonic measuring device (V.A.G 1842).
• Assembly of hose connections with connection couplings. Refer to => [ Air Guide Pipes and Hoses with Connector Coupling ] Service and Repair.
• A small quantity of air dissipates via valves in engine. A pressure retention test is not possible for this reason.
• Handling instructions of (V.A.G 1842) see the Owner's Manual.
• Before removing adapter, discharge pressure in testing circuit by pulling off coupling from (V.A.G 1687/5).
• Hose connections and charge air system hoses must be free of oil and grease before installing.