Scan Tool Data Definitions
Scan Tool Data Definitions
A/C Clutch-Actual
- The scan tool displays On/Off. The HVAC control module displays On when the ECM transmits a class 2 message that the A/C compressor clutch relay is energized.
A/C Clutch-Desired
- The scan tool displays Yes/No. The scan tool displays Yes when the HVAC control module determines that conditions for compressor clutch engagement are present.
A/C High Side Pressure
- The scan tool displays 0-3450 kPa (0-500 psi). The voltage applied to the ECM input from the A/C refrigerant pressure sensor is converted to a pressure value.
A/C High Side Pressure
- The scan tool displays 0-5 volts. The voltage applied to the ECM input for the A/C refrigerant pressure sensor.
A/C Pressure
- The scan tool displays 0-3450 kPa (0-500 psi). The voltage applied to the ECM input from the A/C refrigerant pressure sensor is converted to a pressure value and transmitted in a class 2 message to the HVAC control module.
A/C Relay Command
- The scan tool displays On/Off. The scan tool displays the control decision for the compressor clutch relay output as determined by the ECM.
A/C Request Signal
- The scan tool displays Yes/No. The scan tool displays Yes when the ECM receives a class 2 message from the HVAC control module to engage the A/C compressor clutch. The scan tool displays No when the ECM receives a class 2 message from the HVAC control module to disengage the A/C compressor clutch.
Commanded Blower
- The scan tool displays 0-100%. The scan tool displays the control decision for the blower motor speed as determined by the HVAC control module. The scan tool displays 100% when the blower motor is commanded to maximum speed. The scan tool displays 0% when the blower motor is commanded OFF.
Coolant Temperature
- The scan tool displays -39 to 140°C (-38 to 284°F). The voltage applied to the ECM input from the engine coolant temperature sensor is converted to a temperature value and transmitted in a class 2 message to the HVAC control module.
Driver Temp Dr. Actual
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the driver air temperature door position input of the HVAC control module.
Driver Temp Dr. Commanded
- The scan tool displays 0-255 counts (0-5.00 Volts). The desired position of the driver air temperature actuator as determined by the HVAC control module.
Driver Solar Sensor
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the driver sunload input of the HVAC control module.
Driver Sunload
- The scan tool displays 0-2000 w/m2. The voltage applied to the driver sunload input of the HVAC control module converted to light intensity units.
ECT Sensor
- The scan tool displays -39 to 140°C (-38 to 284°F). The voltage applied to the ECM input from the engine coolant temperature sensor is converted to a temperature value.
ECT Sensor
- The scan tool displays 0-5 volts. The voltage applied to the ECM input for the engine coolant temperature sensor.
Evaporator Temp
- The scan tool displays -39 to 140°C (-38 to 284°F). The voltage applied to the HVAC control module input from the evaporator temperature sensor is converted to a temperature value.
Evaporator Temp
- The scan tool displays 0-255 counts (0-5 Volts). The voltage applied to the HVAC control module input for the evaporator temperature sensor.
Htr./Def./A/C Dr. Actual
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the mode door position input of the HVAC control module.
Htr./Def./A/C Dr. Commanded
- The scan tool displays 0-255 counts (0-5.00 Volts). The desired position of the mode actuator as determined by the HVAC control module.
Inside Air Temp.
- The scan tool displays -40 to 215°C (-40 to 419°F). The voltage applied to the HVAC control module input for the inside air temperature sensor is converted to a temperature value.
Inside Air Temp.
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the HVAC control module input for the inside air temperature sensor.
Low Coolant Status
- The scan tool displays OK/Low. The filtered state of the low coolant switch.
Low Coolant Switch
- The scan tool displays Open/Closed. The actual state of the low coolant switch.
Outside Air Temp.
- The scan tool displays -40 to 215°C (-40 to 419°F). The current value of the ambient air temperature display on the HVAC control module.
Outside Air Temp.
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the HVAC control module input for the outside air temperature sensor.
Passenger Solar Sensor
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the passenger sunload input of the HVAC control module.
Passenger Sunload
- The scan tool displays 0-2000 w/m2. The voltage applied to the driver sunload input of the HVAC control module converted to light intensity units.
Passenger Temp Dr. Actual
- The scan tool displays 0-255 counts (0-5.00 Volts). The voltage applied to the passenger air temperature door position input of the HVAC control module.
Passenger Temp Dr. Commanded
- The scan tool displays 0-255 counts(0-5.00 Volts). The desired position of the passenger air temperature actuator as determined by the HVAC control module.
Pressure Sensor
- The scan tool displays OK/Failed. The state of the A/C refrigerant pressure sensor and circuitry.