Reset Procedure
Re-Calibrating Actuators
Calibration Procedure
Use the following steps to perform the calibration update:
1. Install a scan tool.
2. Turn ON the ignition, with the engine OFF.
3. With a scan tool, select HVAC Systems Manual.
4. Select Special Functions
5. Select HVAC Control Module
6. Select recalibrate All Motors
7. Select ON, wait 60 seconds.