HVAC Control Components

HVAC CONTROL MODULE




The HVAC control module is a class 2 device that interfaces between the operator and the HVAC system to maintain air temperature and distribution settings. The battery positive voltage circuit provides power that the control module uses for Keep Alive Memory (KAM). If the battery positive voltage circuit loses power, all HVAC DTCs and settings will be erased from KAM. The Body Control Module (BCM), which is the vehicle mode master, provides a device on signal. The control module supports the features.

AUXILIARY HVAC CONTROL MODULE - VIN 6
The auxiliary HVAC control module is a class 2 device that interfaces between the rear seat occupants and the auxiliary HVAC system to maintain auxiliary air temperature and auxiliary air distribution settings. The battery positive voltage circuit provides power that the control module uses for keep alive memory (KAM). If the battery positive voltage circuit loses power, all auxiliary HVAC DTCs and settings will be erased from KAM. The auxiliary HVAC control module will perform a recalibration of the electric actuators when commanded with a scan tool or if KAM is lost. This will ensure the actuators are moving with in the calibrated range.

AIR TEMPERATURE ACTUATOR
The air temperature actuators are a 5 wire bi-directional electric motor that incorporates a feed back potentiometer. Ignition 3 voltage, low reference, control, 5 volt reference and position signal circuits enable the actuator to operate. The control circuit uses either a 0, 2.5 or 5 volt signal to command the actuator movement. When the actuator is at rest, the control circuit value is 2.5 volts. A 0 or 5 volt control signal commands the actuator movement in opposite directions. When the actuator shaft rotates, the potentiometer's adjustable contact changes the door position signal between 0-5 volts.

The HVAC control module uses a range of 0-255 counts to index the actuator position. The door position signal voltage is converted to a 0-255 count range. When the module sets a commanded, or targeted, value, the control signal is changed to either 0 or 5 volts depending upon the direction that the actuator needs to rotate to reach the commanded value. As the actuator shaft rotates the changing position signal is sent to the module. Once the position signal and the commanded value are the same, the module changes the control signal to 2.5 volts.

AUXILIARY AIR TEMPERATURE ACTUATOR - VIN 6
The auxiliary air temperature actuator is a 5 wire bi-directional electric motor that incorporates a feedback potentiometer. Low reference, 5 volt reference, position signal, and two control circuits enable the actuator to operate. The control circuits use either a 0 or 12 volt value to co-ordinate the actuator movement. When the actuator is at rest, both control circuits have a value of 0 volts. In order to move the actuator, the auxiliary HVAC control module grounds one of the control circuits while providing the other with 12 volts. The control module reverses the polarity of the control circuits to move the actuator in the opposite direction. When the actuator shaft rotates, the potentiometer's adjustable contact changes the door position signal between 0-5 volts.

The auxiliary HVAC control module uses a range of 0-255 counts to index the actuator position. The door position signal voltage is converted to a 0-255 count range. When the module sets a commanded, or targeted, value, one of the control circuits is grounded. As the actuator shaft rotates the changing position signal is sent to the module. Once the position signal and the commanded value are the same, the module grounds both control circuits.

A/C REFRIGERANT PRESSURE SENSOR
The A/C refrigerant pressure sensor is a 3 wire piezoelectric pressure transducer. A 5 volt reference, low reference, and signal circuits enable the sensor to operate. The A/C pressure signal can be between 0-5 volts. When the A/C refrigerant pressure is low, the signal value is near 0 volts. When the A/C refrigerant pressure is high, the signal value is near 5 volts. The PCM converts the voltage signal to a pressure value.

The A/C refrigerant pressure sensor protects the A/C system from operating when an excessively high pressure condition exists. The PCM disables the compressor clutch if the A/C pressure is more than 2957 kPa (429 psi). The clutch will be enabled after the pressure decreases to less than 1578 kPa (229 psi).

A/C LOW PRESSURE SWITCH
The A/C low pressure switch protects the A/C system from a low pressure condition that could damage the A/C compressor or cause evaporator icing. The HVAC control module applies 12 volts to the A/C low pressure switch signal circuit. The switch will open when the A/C low side pressure reaches 124 kPa (18 psi). This prevents the A/C compressor from operating. The switch will then close when A/C low pressure side reaches 275 kPa (40 psi). This enables the A/C compressor to turn back ON.

COOLANT BYPASS VALVE
The coolant bypass valve controls coolant flow to the auxiliary heater core. Integral to the coolant bypass valve is an electric solenoid that controls vacuum flow to open and close the valve. When the HVAC control module applies 12 volts to the integral solenoid, the solenoid applies vacuum to a diaphragm that closes the water valve. This action restricts coolant flow to the auxiliary heater core. The coolant bypass valve is normally open to allow coolant flow.