Ambient Temperature Sensor / Switch HVAC: Testing and Inspection
Wiring Diagram:
1. Remove front radiator grille.
2 Disconnect ambient temperature sensor connector.
3. Check resistance between terminals 1 and 2 of ambient temperature sensor connector at each temperature.
RESISTANCE:
At 25°C (77°F) 1.6 - 1.8 K Ohms
At 50°C (122°F) .05 - .07 K Ohms
HINT: As the temperature increases, the resistance decreases.
4. If the sensor fails this test replace the room temperature sensor.