Compressor HVAC: Testing and Inspection
A/C COMPRESSOR - EXTERNAL LEAK TEST1. Install the A/C Pressure Test Adapter on the port of the A/C compressor, using the existing manifold retaining bolt.
2. Connect the high and low pressure lines of a manifold gauge set or a refrigerant recovery/recycling station such as the R-134a A/C service center to the corresponding fittings on the A/C Pressure Test Adapter.
3. Attach the center hose of a manifold gauge set to a refrigerant container standing in an upright position.
4. Hand-rotate the compressor shaft 10 complete revolutions to distribute the oil inside the A/C compressor.
5. Open the low pressure gauge valve, the high pressure gauge valve and the valve on the refrigerant container to allow the refrigerant vapor to flow into the A/C compressor.
6. Using the Refrigerant Leak Detector, check for leaks at the compressor shaft.
7. If a shaft seal or external leak is found, install a new A/C compressor.
8. When the leak test is complete, recover the refrigerant from the compressor.