Compressor HVAC: Testing and Inspection
Climate Control System
Component Tests
A/C Compressor - External Leak Test
1. Install the adapter from the A/C Flush Adapter Kit on the port of the A/C compressor, using the existing manifold retaining bolt.
2. Connect the high and low pressure lines of a manifold gauge set or a refrigerant recovery/recycling station to the corresponding fittings on the adapter.
3. Attach the center hose of a manifold gauge set to a refrigerant container standing in an upright position.
4. Open the low pressure gauge valve, the high pressure gauge valve and the valve on the refrigerant container to allow the refrigerant vapor to flow into the A/C compressor.
5. Using the Refrigerant Leak Detector, check for leaks at the compressor shaft.
6. If an external leak is found, install a new A/C compressor.
7. When the leak test is complete, recover the refrigerant from the compressor.