Compressor Control
SYSTEM
Compressor Control
DESCRIPTION
- When the compressor activation condition is satisfied while blower motor is activated, A/C auto amp. transmits A/C ON signal and blower fan ON signal to BCM.
- BCM transmits the A/C ON signal and blower fan ON signal to ECM via CAN communication line. Refer to
With Intelligent Key System.
- ECM judges the conditions of each sensor (Refrigerant pressure sensor signal, accelerator position signal, etc.), and transmits the A/C compressor request signal to IPDM E/R via CAN communication line.
- By receiving the A/C compressor request signal from ECM, IPDM E/R turns the A/C relay to ON, and activates the compressor. IPDM E/R (With I-Key).
CONTROL BY A/C AUTO AMP.
Low Temperature Protection Control
When intake sensor detects that evaporator fin temperature is 2�C
(36�F) or less, A/C auto amp. requests ECM to turn the compressor
OFF, and stops the compressor.
When the air temperature returns to 3.5�C (38�F) or more, the compressor is activated.
CONTROL BY ECM
Compressor Protection Control at Pressure Malfunction
When the high-pressure side value that is detected by refrigerant pressure sensor is as per the following state, ECM requests IPDM E/R to turn A/C relay OFF and stops the compressor.
- 3.12 MPa (31.82 kg/cm2, 452.4 psi) or more (When the engine speed is less than 1,500 rpm)
- 2.74 MPa (27.95 kg/cm2, 397.3 psi) or more (When the engine speed is 1,500 rpm or more)
- 0.14 MPa (1.43 kg/cm2, 20.3 psi) or less Compressor Oil Circulation Control
When the engine starts while the engine coolant temperature is 56�C (133�F) or less, ECM activates the compressor for approximately 6 seconds and circulates the compressor oil once.
Air Conditioning Cut Control
When the engine condition is high load, ECM transmit A/C relay OFF request to IPDM E/R, and stops the compressor. System Description.