Test Point 2
Test point 2
Outside temperature sensor
Open circuit Short to ground
Fault code 21
Diagnosis conditions
No control module fault stored.
No fault with supply voltage (5 volts).
Open circuit
1. Unplug connector A from the heating/air-conditioning control.
2. Connect ohmmeter to connectors A 7 and A 12.
Display: approx. 1.2 kOhms at 23 °C
3. Unplug connector from the outside temperature sensor.
4. Connect ohmmeter to connector A 7 and pin 1 (connector of outside temperature sensor).
Display: 0 - 5 Ohms
5. Connect ohmmeter to connector A 12 and pin 2 (connector of outside temperature sensor).
Display: 0 - 5 Ohms
6. Connect voltmeter to connector A 7 and ground. Switch on ignition.
Display: 0 volts
If approx. 5 volts are displayed, check wiring harness for pinching and chafing damage.
Short to ground
1. Unplug connector A from the heating/air-conditioning control.
2. Connect ohmmeter to connector A 7 and ground.
Display: Infinity ohm
If 0 - 5 Ohms is displayed, check wiring harness for pinching and chafing damage.