Specific System Condition - TXV Open
Specific System Condition - TXV Open - L61:
KEY:
1. HIGHER THAN NORMAL SUCTION PRESSURE.
2. HIGHER THAN NORMAL OUTLET TEMPERATURE.
THEN: Thermal Expansion Valve (TXV) may he open.
^ This condition can lead to compressor chatter due to oil being flushed from the compressor.
^ Replace TXV.
^ After repair return to diagnostic flow chart.Diagnostic Flow Chart