Operation CHARM: Car repair manuals for everyone.

Refrigerant Charging Procedure

Refrigerant Charging Procedure

PROCEDURE

CAUTION:
- During operation, be sure to wear protective goggles and protective gloves.
- Before charging the refrigerant, evacuate the system to remove small amounts of moisture remaining in the system. The moisture in the system can be completely evacuated only under the minimum vacuum level. The minimum vacuum level affects the temperature in the system.
- The list below shows the vacuum values necessary to boil water at various temperatures. In addition, the vacuum levels indicated on the gauge are approx. 3.3 kPa (25 mmHg, 0.98 inHg) lower than those measured at 304.8 m (1,000 ft) above sea level.







1. Close the valves on low-/high-pressure sides of the manifold gauge.






2. Install the low-/high-pressure hoses to the corresponding service ports on the vehicle.
3. Connect the center hose of the manifold gauge set with the vacuum pump.
4. Carefully open the valves on the low-/high-pressure sides to activate the vacuum pump.






5. After the low-pressure gauge reaches 100.0 kPa (750 mmHg, 29.5 in Hg) or higher, evacuate the system for approx. 15 minutes. (Continue evacuation).






6. After 15 minutes of evacuation, if the reading shows 100.0 kPa (750 mmHg, 29.5 in Hg) or higher, close the valves on the both sides to stop the vacuum pump.






7. Note the low-pressure gauge reading.






8. Leave it at least 5 minutes, and then check the low-pressure gauge reading for any changes. If the gauge indicator shows near zero point, it is a sign of leakage. Check pipe connector points, repair them, and make sure there is no leakage.
9. Follow the can tap operation manual, install to the refrigerant can.






10. Disconnect the center manifold hose from the vacuum pump, and connect the hose to the tap valve.
11. When a 13.6 kg (30 lb) refrigerant container is used, measure the weight of the refrigerant amount to use using a scale.






12. Confirm that all the 3 hoses are connected securely to the manifold gauge set.






13. Open the valve on the HFC-134a source.
14. Loosen the center hose connection on the manifold gauge set (if applicable, press a purge valve on the manifold gauge set) for a few seconds to discharge the air in the center hose by the refrigerant pressure.
15. Stop the engine and carefully open the high pressure valve.

CAUTION: Do not open the low-pressure valve.






CAUTION: Never run the engine while charging from the high-pressure side.

16. Close the high-pressure valve when the low pressure gauge reaches 98 kPa (1 kg/sq.cm, 14 psi). Using a leak tester, check the system for leaks. If any leakage is found after the refrigerant recovery is completed, repair the applicable area.
17. After confirming that there are no leaks with the leak test, charge the required amount of refrigerant.

CAUTION: Never run the engine while charging from the high-pressure side.

18. Close the high-pressure valve when;
- the readings of low- / high-pressure gauges become almost equal, after the charging speed is reduced,
- the HFC-134a source becomes empty, or the system is full with the gas.






19. If the HFC-134a source is empty, close the high-pressure valve, close the valve on the can tap, and replace the HFC-134a source with a new part to restart the operation.






NOTE: When replacing HFC-134a source with a new part, loosen the center hose connection on the manifold gauge set (if applicable, press a purge valve on the manifold gauge set) for a few seconds to discharge the air in the center hose by the refrigerant pressure.

20. Confirm that both the low- / high-pressure valves can be closed. Start the engine with the A/C switch OFF.
21. Quickly repeat ON-OFF cycles a few times to prevent initial compressor damage.
22. Set up the vehicle as follows:
- A/C switch ON
- Engine running at 1,500 rpm
- Blower setting speed"HI") (For models with rear coolers, also turn the rear cooler fan switch to"HI")
- Temperature setting to"MAX COOL"
- Air inlet setting to"RECIRC"
- Window open

23. While reading the low-pressure gauge, carefully open the low-pressure valve with the refrigerant source connected and the service hose purged.

CAUTION: Never open the high-pressure valve with the engine running. The high-pressure gas will backflow resulting in an explosion of the can.






24. Adjust the refrigerant flow to maintain the pressure on the low-pressure side at 276 kPa (2.81 kg/sq.cm, 40 psi) max.
25. After the system is fully charged, close the low pressure valve.
26. Close the valve on the refrigerant source.






27. Disconnect the hose from the service port, and install the service port cap.