Test D1: Pressure Cycling Switch
D1: Checking the condition of the Pressure Cycling Switch.^ Remove the connector from the suspect switch and connect a fused jumper between the terminals of the connector.
^ If battery voltage is present at terminal 1 of the A/C Cut-Out Relay with the jumper connected, Refer to System Diagnosis / Procedures / Functional Test for procedure to check refrigerant charge. Testing and Inspection
^ If refrigerant charge is normal, replace the suspect switch. If refrigerant charge is low, Refer to Service and Repairs to evacuate and recharge. Service and Repair