Refrigerant Pressure Sensor Inspection [Manual Air Conditioner]
REFRIGERANT PRESSURE SENSOR INSPECTION [MANUAL AIR CONDITIONER]
1. Install the manifold gauge.
2. Verify the high-pressure side reading of the manifold gauge.
3. Measure the terminal voltage of the PCM.
- 1AR, 1J or 1AE (L5)
- 1AT, 1M or 1BJ (MZI-3.7)
4. Verify that below graph as measure the terminal voltage 1J (L5), 1M (MZI-3.7).
5. Follow the PCM inspection when measure the other terminal voltage. Component Tests and General Diagnostics Component Tests and General Diagnostics
- Terminal 1AR (L5), 1AT (MZI-3.7): 1.0 V or less
- Terminal 1AE (L5), 1BJ (MZI-3.7): Approx. 5 V (Ignition switch on)
- If the each voltage is not normal, inspect the related wiring harness.
- If there is any malfunction, replace the related wiring harness.
- If wiring harness is normal, replace the refrigerant pressure sensor.
L5
MZI-3.7