With Monochrome Display
INSPECTION AND ADJUSTMENT
Temperature Setting Trimmer
Description
If the temperature felt by the customer is different than the airflow temperature controlled by the temperature setting, the auto amplifier control temperature can be adjusted to compensate for the temperature setting.
How to set
Using CONSULT-III, perform "TEMP SET CORRECT" in "WORK SUPPORT" of HVAC.
NOTE:
- When the temperature setting is set to 25.0�C (77�F) and -3.0�C (-6�F), the temperature controlled by auto amp is 25.0�C (77�F) - 3.0�C (6�F) = 22.0�C (71�F) and the temperature becomes lower than the temperature setting.
- When the battery cable is disconnected from the negative terminal or when the battery voltage becomes 10V or less, the setting of the difference between the temperature setting and control temperature may be cancelled.